8. ENGINEERING MODE
IMR01N12-E7
64
Continued from the previous page.
Bar graph display explanation:
Manipulated output value (MV)
display
Displays the Manipulated output value (MV). When Manipulated output value (MV) is
at 0 % or less, the left-end dot of the bar-graph flashes. When MV exceeds 100 %,
the right-end dot flashes.
Measured value (PV) display
Scaling is available within the input range.
Set value (SV) display
Displays the Set value (SV). Scaling is available within the input range.
Deviation value display
Displays the deviation between the Measured value (PV) and the Set value (SV).
When the Deviation display is selected, the dots at both ends of bar-graph light.
A display resolution per dot is settable from 1 to 100.
The number of dot points: 10 dots (HA430)
20 dots (HA930)
Bar graph resolution setting (dEUT)
Use to set the bar graph display resolution for the deviation display. Set several digits per 1 dot of the bar graph.
Data range:
1 to 100 digit/dot
Factory set value:
100
Related parameters:
Bar graph display selection (P. 63)
Decimal point position of MV scaling (MVdP)
Use to select the decimal point position of the MV scaling function.
Data range:
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Factory set value:
1
Related parameters:
MV scaling high (P. 64), MV scaling low (P. 65)
MV scaling function:
The MV scaling function is used to make scaling of Manipulated output value 1 (MV1)
from 0 to 100 % between the high and low MV scaling limits as the RPM of extruder’s
main motor.
MV scaling high (MVHS)
This value is to set the high limit value of MV scaling monitor value. Set the motor RPM when MV1 = 100 %.
Data range:
1999.9 to
9999.9
Factory set value:
100.0
Related parameters:
Decimal point position of MV scaling (P. 64), MV scaling low (P. 65)
MV scaling monitor value is displayed on the SV of PV1/SV1 monitor screen (P. 102).
0
[Display example]
[Display example]
0
50
100
[Display example]
0
50
100
[Display example]
0
50
100