6. PARAMETER SETTING MODE
6.1 Display Sequence
In Parameter setting mode, the following operations are possible. Set parameters relating to control such as PID
constants, Event set values, and the Setting change rate limiter. To go to Parameter setting mode, press and hold
the SET key for 2 seconds at SV setting & Monitor mode or Setup setting mode. Up to 16 individual sets of SVs
and parameters in Parameter setting mode can be stored and used in Multi-memory area function. Ramp/Soak
control is possible by using Area soak time, Link area number and Setting change rate limiter (up/down) in
Parameter setting mode.
or
SV setting & Monitor mode
Setup setting mode
Press and hold the SET key for 2 seconds
Event 1 set value (EV1)
SET key
SET key
SET key
AREA
Event 2 set value (EV2)
AREA
(When LBA is selected in Event 3 or Event 4)
Event 3 set value (EV3)
AREA
Control loop break alarm 1 (LBA1)
time
AREA
SET key
SET key
Event 4 set value (EV4)
AREA
LBA1 deadband
AREA
SET key
AREA
SET key
LBA2 deadband
AREA
SET key
Input 1_proportional band
SET key
Input 1_integral time
SET key
Input 1_derivative time
AREA
AREA
AREA
SET key
SET key
Continued on the next page
*
*For 1-input controller: To Input 1_setting change rate limiter (up) screen
For 2-input controller: To Input 2_proportional band screen
Input 1_control response
parameter
AREA
Control loop break alarm 2 (LBA2)
time
(P.35)
(P.35)
(P.35)
(P.35)
(P.37)
(P.37)
(P.37)
(P.38)
(P.35)
(P.36)
(P.35)
(P.36)
: Parameters related to multi-memory area function
: Parameters displayed when function is specified.