8. ENGINEERING MODE
IMR01N12-E7
88
ON/OFF action differential gap (upper) (1. oHH, 2. oHH)
Use to set the ON/OFF control differential gap (upper).
Data range:
0 to Input span
(Varies with the setting of the Decimal point position)
Factory set value:
Input 1_ON/OFF action differential gap (upper) (1. oHH):
Pressure sensor input:
1.0 MPa
Voltage (V)/Current (I) inputs: 0.1 % of input span
Input 2_ON/OFF action differential gap (upper) (2. oHH):
TC/RTD
inputs:
1.0
C [
F]
Voltage (V)/Current (I) inputs: 0.1 % of input span
Related parameters:
ON/OFF action differential gap (lower) (P. 88)
ON/OFF Action Differential Gap:
ON/OFF control is possible when the Proportional band is set to “0” or “0.0.” In
ON/OFF control with Reverse action, when the Measured value (PV) is smaller than
the Set value (SV), the Manipulated output (MV) is 100 % or ON. When the PV is
higher than the SV, the MV is 0 % or OFF. Differential gap setting prevents control
output from repeating ON and OFF too frequently.
Differential gap
(Upper)
Set value (SV)
Manipulated output
value (MV)
Time
ON
OFF
ON
OFF
ON OFF
Differential gap
(Lower)
ON/OFF action differential gap (lower) (1. oHL, 2. oHL)
Use to set the ON/OFF control differential gap (lower).
Data range:
0 to Input span
(Varies with the setting of the Decimal point position)
Factory set value:
Input 1_ON/OFF action differential gap (lower) (1. oHL):
Pressure sensor input:
1.0 MPa
Voltage (V)/Current (I) inputs: 0.1 % of input span
Input 2_ON/OFF action differential gap (lower) (2. oHL):
TC/RTD
inputs:
1.0
C [
F]
Voltage (V)/Current (I) inputs: 0.1 % of input span
Related parameters:
ON/OFF action differential gap (upper) (P. 88)
Description of function:
Refer to
ON/OFF action differential gap (upper)
.