7. Maintenance
7-9 Making changes in Environmental setting 1
99 / 191
7-9 Making changes in Environmental setting 1
The following items can be set in Environmental setting 1:
LCD display
Setting item
Remarks
2- 9 SETTING1
Environmental setting 1
SET- 0 INHIBIT
INHIBIT setting
SET- 1 ALM P
ALARM SETTING
SET- 2 ALM DLY
ALARM DELAY SETTING
SET- 3 MAINTE
Maintenance
Refer to ‘8. Replacing and cleaning
parts’.
SET- 4 F TEST
Fault test
SET- 5 OPT ACT
TERMINAL UNIT
SETTING
7-9-1 INHIBIT setting (INHIBIT)
Set ON/OFF for INHIBIT for each sensor.
Set to ON to disable external alarm signal output even when gas concentrations exceed the alarm
setpoints in detection mode. This setting is primarily used when testing and inspecting the product.
When all of the sensors are set to ON, the fault alarms and cautions on the main unit also stop being
issued.
The default setting is OFF.
1 In maintenance mode, press the
▲
key or
▼
key
to select [2- 9 SETTING1], then press the
TEST/SET key.
2 Select [SET- 0 INHIBIT] and press the TEST/SET
key.
EA
4-20mA