background image

  

 

00304

 

AGDS-MCM 

v2

 

 

• 

Gas Detection . (Up to 16 detectors, with power pack) 

• 

Natural gas, LPG, carbon monoxide & carbon dioxide 

• 

Remote emergency stops 

• 

Fire Alarm input monitoring 

• 

BMS relay (Settable) 

• 

5 year warranty  - 10 years when commissioned 

AGDS-MCM features 

Installation Instructions 

 
The AGDS-MCM 

v2

 is a multi channel gas detection system designed for monitoring gas build-up. Six low 

voltage detectors can be connected (16 with a power pack) for the detection of natural gas, LPG, or carbon 
monoxide, carbon dioxide and oxygen depletion. 
 
In the event of a high alarm from one of the detectors, the system will alarm. Low alarm indication is also 
given. 
 
Even with the system switched off It can still be used to monitor for carbon monoxide and dioxide via its 0-
10v output and BMS relays. Should there be an issue from a solid fuel appliance it can raise an alarm or 
switch ventilation on via a relay. 

Before commencing installation please familiarise yourself to the equipment by reading the comprehensive 
installation instructions. If in doubt then please call 0161 233 0600. Out of hours please call 07894 684080 or 
07843 355163. 
 

 

It is a statutory requirement that this safety system is installed and commissioned 

to the satisfaction of the manufacturer. 

 

 

A commissioning certificate must be issued to the end user along with instructions for the operation of the 
equipment. 
 
As the Manufacturer, Medem UK should commission this safety system whereupon a commissioning report 
will be forwarded to the installing agent who should provide a copy to the end user.  
At the point of our commissioning an individual serial number will be attached to the system along with a 24 
help line number. Photos and all relevant information for the installation will then be stored on the Medem 
site database to be accessed in the event of a call on the 24 hour help line. The warranty period for the pan-
el and sender unit will then be extended to Ten years.

 

Содержание AGDS-MCM v2

Страница 1: ...ilation on via a relay Before commencing installation please familiarise yourself to the equipment by reading the comprehensive installation instructions If in doubt then please call 0161 233 0600 Out...

Страница 2: ...tors are set to alarm at 5 LEL pre alarm and 10 LEL for the high alarm Carbon Monoxide detectors are set to alarm at 20ppm pre alarm and 30ppm for high alarm Carbon Dioxide detectors have settable hig...

Страница 3: ...0 10 volt output to fan speed controllers based on CO2 and temperature levels 15 SELV Output for low power beacons toners Set using switch 26 16 Enable Disable internal toner 17 BMS relays settings f...

Страница 4: ...lways recommend using screen cable if the distance between the main panel and the detectors is greater than 20metres a 1mm screened cable must be used on the VE 0v terminals Gas detectors require a fo...

Страница 5: ...ould be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indic...

Страница 6: ...here are five relays on the system which can be used for connecting to a BMS or sounder Beacon etc these can be set for switching to various conditions using the table below There are two mains rated...

Страница 7: ...ngs Medem UK Ltd would always recommend an onsite risk assessment be carried out before any changes are implemented 28 OPT A Spare OPT B Auto restart on power failure and fire alarm off by default 2MA...

Страница 8: ...gas that is being monitored for See the gas detectors own instructions for more guidance VE supply Comm s From either the main panel Address Selector Each detector must be set to its own address And...

Страница 9: ...bove standing head height and between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilat...

Страница 10: ...plier Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will car...

Страница 11: ...this once allows the panel to learn how many and which type of detectors are fitted 8 Press the Detectors button on the front panel and check on the display that all the detectors have been recognise...