 4

 

00258

 

Addressable Gas 

detector 

 

Address 

And then press Learn 

(

21

Wire multiple detectors 

in parallel 

Earth Connections not shown 

11

9  10 

13 

12 

14 

17 

15 

Schematic

 

AGDS-MCM 

v2

 

230v Supply 

3Amp Fused Spur 

EM Stop  Buttons, 

Thermal links  

(Normally closed) 

 

For multiple, connect in 

series.  

AUX 1 & AUX 2 

Mains Rated  

Potential free contact,  

Max  load 5amp’s 

(latching relay) 

See page 6 

    Basic connections 

All current wiring regulations must be followed with reference to running low and mains voltage cables together. 
The maximum cable length between a detector  and the control panel should not exceed 100 metres, whilst we would 
always recommend using screen cable if the distance between the main panel and the detectors is greater than 20metres a 
1mm screened cable must be used on the +VE, 0v terminals 

 

Gas detectors, require a four core screened Belden type security cable or 600v rated BMS cable (max cable length of 
100meters.)  
Remote emergency stops and thermal links require a two core screened cable. 
Warranty will be void if Fire Protection Cable or cable over 1mm dia. is used on the SELV side. 

(

8,9

Optional Ventilation 

Interlock connections 

(

13

Fire alarm connection 

Requires a N/C contact 

in the fire panel 

18 

Optional 

Switchable contact for 

controlling an electrical 

contactor etc 

0 to 10v output for connection 

to a fan speed controller 

For use in conjunction with 

Co2 detection 

Nominal 20v supply 
Set using DIP switch  

V BMS (

26

See page 6 for settings 

Содержание AGDS-MCM v2

Страница 1: ...ilation on via a relay Before commencing installation please familiarise yourself to the equipment by reading the comprehensive installation instructions If in doubt then please call 0161 233 0600 Out...

Страница 2: ...tors are set to alarm at 5 LEL pre alarm and 10 LEL for the high alarm Carbon Monoxide detectors are set to alarm at 20ppm pre alarm and 30ppm for high alarm Carbon Dioxide detectors have settable hig...

Страница 3: ...0 10 volt output to fan speed controllers based on CO2 and temperature levels 15 SELV Output for low power beacons toners Set using switch 26 16 Enable Disable internal toner 17 BMS relays settings f...

Страница 4: ...lways recommend using screen cable if the distance between the main panel and the detectors is greater than 20metres a 1mm screened cable must be used on the VE 0v terminals Gas detectors require a fo...

Страница 5: ...ould be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indic...

Страница 6: ...here are five relays on the system which can be used for connecting to a BMS or sounder Beacon etc these can be set for switching to various conditions using the table below There are two mains rated...

Страница 7: ...ngs Medem UK Ltd would always recommend an onsite risk assessment be carried out before any changes are implemented 28 OPT A Spare OPT B Auto restart on power failure and fire alarm off by default 2MA...

Страница 8: ...gas that is being monitored for See the gas detectors own instructions for more guidance VE supply Comm s From either the main panel Address Selector Each detector must be set to its own address And...

Страница 9: ...bove standing head height and between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilat...

Страница 10: ...plier Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will car...

Страница 11: ...this once allows the panel to learn how many and which type of detectors are fitted 8 Press the Detectors button on the front panel and check on the display that all the detectors have been recognise...

Отзывы: