AGDS-MCM 

v2

 

Remote stop buttons

 

To EM Stop connections in the 

panel 

Use terminals TB2 A & C 

Use terminals TB2 A & C 

Remote stop buttons can be  connected to the panel terminal 
marked as “EM STOP” (number 7 ).  
 
The remote buttons must be wired as shown in order to provide a 
“closed contact” for the control panel. 

 
If thermal links are to be installed these should be wired 
in series with the EM stop buttons 

To EM Stop connections in the 

panel 

Indicator bar shows when 
pressed 

Normal 

EM-Stop Activated 

    Multiple Stop Buttons 

    Single Stop Buttons 

     Resetting (indicator bar) 

The stop buttons supplied by Medem are of a “Push Glass, key resettable” style, when activated a yellow indicator bar will 
show and the unit will require resetting using the key provided. 

Multiple stop buttons are wired in series. 
 
If thermal links are to be installed these too should 
be wired in series with the EM stop buttons 
 

Use terminal TB2 A & C 

Содержание AGDS-MCM v2

Страница 1: ...ilation on via a relay Before commencing installation please familiarise yourself to the equipment by reading the comprehensive installation instructions If in doubt then please call 0161 233 0600 Out...

Страница 2: ...tors are set to alarm at 5 LEL pre alarm and 10 LEL for the high alarm Carbon Monoxide detectors are set to alarm at 20ppm pre alarm and 30ppm for high alarm Carbon Dioxide detectors have settable hig...

Страница 3: ...0 10 volt output to fan speed controllers based on CO2 and temperature levels 15 SELV Output for low power beacons toners Set using switch 26 16 Enable Disable internal toner 17 BMS relays settings f...

Страница 4: ...lways recommend using screen cable if the distance between the main panel and the detectors is greater than 20metres a 1mm screened cable must be used on the VE 0v terminals Gas detectors require a fo...

Страница 5: ...ould be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indic...

Страница 6: ...here are five relays on the system which can be used for connecting to a BMS or sounder Beacon etc these can be set for switching to various conditions using the table below There are two mains rated...

Страница 7: ...ngs Medem UK Ltd would always recommend an onsite risk assessment be carried out before any changes are implemented 28 OPT A Spare OPT B Auto restart on power failure and fire alarm off by default 2MA...

Страница 8: ...gas that is being monitored for See the gas detectors own instructions for more guidance VE supply Comm s From either the main panel Address Selector Each detector must be set to its own address And...

Страница 9: ...bove standing head height and between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilat...

Страница 10: ...plier Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will car...

Страница 11: ...this once allows the panel to learn how many and which type of detectors are fitted 8 Press the Detectors button on the front panel and check on the display that all the detectors have been recognise...