4. Installation
4-6 Wiring procedure
44 / 191
4-6-4 Grounding terminal connections
WARNING
Be sure to ground the product before supplying power.
Ground the product to ensure stable operation and safety. Never connect grounding wires to gas pipes.
Make sure the grounding is Class D or equivalent (grounding resistance not exceeding 100
Ω
).
Use cable lugs on the grounding wire to ensure safe grounding with the cable free of slack and twisting.
Do not ground to or near the same point used to ground other high-frequency devices or high-voltage
devices.
<Connection example: 4 - 20 mA models>
<Connection example: ET models>
GD-84D-EX-EC
GD-84D-EX
Stabilized
power supply
(24 V DC)
Upstream
(DCS, PLC)
GD-84D-EX-ET-EC
GD-84D-EX-ET
Switching hub
(With PoE+
functionality)
Upstream
(PC, PLC)