4. Installation
4-6 Wiring procedure
42 / 191
4-6-2 Terminal plate specifications
<Terminal plate>
1 2 3 4 5 6 7 8 9 10
+
-
+
-
+
-
+
-
+
-
24 V DC
A1
4 - 20 mA
A2
4 - 20 mA
B1
4 - 20 mA
B2
4 - 20 mA
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
A1
ALM1
A1
ALM2
A2
ALM1
A2
ALM2
B1
ALM1
B1
ALM2
B2
ALM1
B2
ALM2
FAULT
NOTE
With EA models, do not use 24 V DC terminals 1 and 2 when using the PoE+ connection.
<Terminal plate specifications>
Rated voltage: 300 V AC
Rated current: 10 A
However, this will vary depending on the cable used.
<Connecting conditions>
Solid wire cable, flexible stranded wire: 0.08 - 2.5 mm
2
Flexible stranded wire fitted with ferrule: 0.25 - 2.5 mm
2
Insulation stripped length: 8 - 9 mm
Tools for connection: Flathead screwdriver (3.5 mm wide or less, 0.5 mm thick or less) (Manufacturer
tool: 210-720)
CAUTION
Be sure to strip the cable to the specified length.
Conduction faults or overheating may result if the stripped wire length is too short and the wire is
clamped incorrectly.
Conduction faults or overheating may result if the stripped wire length is too short and the wire
sheathing is clamped.
An insulation failure or short circuit may result if the stripped wire length is too long and the wire is
exposed.
Make sure the wire does not splay. Insulation failure or overheating may result if the wire splays when
inserted.
4-20mA
EA
8 - 9 mm