7. Maintenance
7-2 Performing alarm tests
79 / 191
7-2 Performing alarm tests
A signal is emitted that simulates a gas concentration, enabling checks of the alarm lamps and the status
of signal transmissions to external devices.
WARNING
Before starting an alarm test, notify the related departments so that measures can be taken to
ensure that problems do not arise due to external output signals or alarm contacts.
When the alarm test is complete, hold down the TEST/SET key to return to the detection mode. The
product will not detect gases while in the adjustment/setting state. If left in alarm test mode, the
product will return to detection mode after 10 hours. Note that this is dangerous because no
monitoring occurs during this time.
1 In detection mode, hold down the TEST/SET key for about 3
seconds.
Switches to alarm test mode.
2 Press
the
▲
key or
▼
key to select the sensor for which
the alarm test is to be performed.
Press the
▲
key or
▼
key repeatedly to cycle through
the following settings: [A1]
⇔
[A2]
⇔
[B1]
⇔
[B2].
The concentration for the selected sensor blinks.
3 Press the TEST/SET key to confirm the sensor to be tested.
4 Press
the
▲
key or
▼
key to set the concentration.
5 Check to confirm that an alarm is triggered.
The first alarm is triggered when the concentration reaches the
first alarm setpoint.
When the first alarm is triggered, the alarm lamp (ALM1) lights
up (red).
When [TEST ON], then the contact of the first alarm is
activated.
Alarm lamp (ALM1)
lights up (red)