5. Usage Instructions
5-1 Preparations for startup
48 / 191
5
Usage Instructions
5-1 Preparations for startup
Perform the following checks before connecting the power supply.
Failure to perform these checks may result in electric shock or damage to the product.
Check to confirm the product is grounded.
Check to confirm that the external wiring is connected correctly.
Check to confirm that the power supply voltage is within the rated range.
External contacts may activate while adjustment is underway.
Take precautions to prevent unwanted consequences due to activated contacts.
Check to confirm that the connected piping is free of blockages and leaks.
Blockages in connected pipes will generate excessive pressure on the sensors, which can lead to
malfunctions or failure. Depending on the sensor, blockages may also cause fluctuations in readings
and false alarms.
If a filter is required, confirm that the correct filter is fitted properly. Make sure the filter is suitable for the
detection target gas.