7. Maintenance
7-10 Making changes in Environmental setting 2
137 / 191
7-10-21 External output during fault setting (FLT OUT)
Set the external output when there is a fault for each sensor.
Select one of the following:
0.5 mA ([0.5])
: Set the external output value to 0.5 mA.
21.5 mA ([21.5]) : Set the external output value to 21.5 mA.
OPT ([OPT])
: Set in the range between 0.0 mA and 4.0 mA. (digit: 0.1)
The default setting is 0.5 mA ([0.5]).
1 In maintenance mode, press the
▲
key or
▼
key to
select [2-10 SETTING2], then press the TEST/SET key.
2 Press
the
▲
key or
▼
key to select [SET-21 FLT OUT],
then press the TEST/SET key.
3 Press
the
▲
key or
▼
key to select the sensor.
Press the
▲
key or
▼
key repeatedly to cycle through the
following settings: [A1]
⇔
[A2]
⇔
[B1]
⇔
[B2].
The setting value for the selected sensor blinks.
4 Press the TEST/SET key to confirm the sensor.
4-20mA
EA