7. Maintenance
7-10 Making changes in Environmental setting 2
117 / 191
<Setting the fault alarm contact>
1 In maintenance mode, press the
▲
key or
▼
key to
select [2-10 SETTING2], then press the TEST/SET key.
2 Select [SET- 6 RLY PTRN], then press the TEST/SET key.
3 Press
the
▲
key or
▼
key to select [FLT RLY], then
press the TEST/SET key.
4 Press
the
▲
key or
▼
key to select [ND] or
[NE], then press the TEST/SET key.
The display reverts to the display in step 3.
5 Press the MODE key.
The display reverts to the [SET- 6 RLY PTRN] display.
6 Press the MODE key.
The display reverts to the [2-10 SETTING2] display.
Содержание GD-84D-EX Series
Страница 192: ...Revision History Issue Revision details Issue date 0 First issue PT2 3041 12 20 2022 ...
Страница 193: ......
Страница 194: ......