CO922  Carbon monoxide Gas Detector

This equipment is designed to protect individuals from acute exposure to carbon monoxide.
This equipment will not completely protect the Individuals with specific medical conditions.
In doubt, consult a doctor.

230 VAC

230 VAC

230 VAC

Important: Assembly / maintenance of the appliance must be carried out by qualified personnel and in
accordance with applicable laws and regulations.
The manufacturer assumes no responsibility for the use of products that have to comply with particular
environmental and / or installation standards.

Important note
Before connecting the equipment, it is recommended that you read the instruction manual carefully and
keep it for future reference. It is also recommended to perform the electrical connections correctly as
per enclosed drawings, observing the instructions and the Standards.
N.B. Refer to the documentation in all cases where the symbol is on the side

Channel:  Beinat  gas  solutions

Electric connections also available on

CONFORMITY

Installation and user
guide

EN 50291
EN 50270

CEI 216-3

EN 61010-1

Installation  EN 60079-29-2

The CO922  detector  has  been  designed  and  built  according  to  European  regulations  to  detect  the
presence of CO toxic gas.
A microprocessor is used to create a complete surveillance and control system with maximum flexibility.
Thanks to this and its other features, this detector is suitable for household applications.
The gas detected by the CO922 is Carbon Monoxide, when both the maximum CO admissible concentration
threshold of 300ppm is exceeded, and when low CO concentrations persist in the environment for lengthy
periods, which according to the principle of accumulation could also damage the human organism.

The probe can activate solenoid valves, sirens, and any other signal or alarm handling devices using the
built-in relay. A series of technical features make this detector extremely versatile, reliable, accurate,
and safe.
The relay, free of voltage, allows installation of multiple detectors on a single solenoid valve or suction
fan, ensuring control of multiple dangerous environments.
The detector is complete with a special circuit that controls the sensor’s efficiency level, and signals any
possible fault. The external container has an IP42 protection degree.

Содержание CO922

Страница 1: ...allation and user guide EN 50291 EN 50270 CEI 216 3 EN 61010 1 Installation EN 60079 29 2 The CO922 detector has been designed and built according to European regulations to detect the presence of CO toxic gas A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features this detector is suitable for household applicati...

Страница 2: ... Power supply 230Vac 50 60 Hz 10 Power consumption 1W Change over relays for CO toxic gas detection 10A 250V resistive Insulation Class II CO toxic gas sensor Electrochemical Cell CO detector alarm sensitivity 30 300ppm CO gas detector alarm threshold according to norm EN 50291 on gas accumulation ALARMS 30 ppm within 120 minutes 50 ppm within 60 minutes 100 ppm within 10 minutes 300 ppm within 3 ...

Страница 3: ... to the fault circuit as well as the light indication and a cricket siren 3 CO ALARM indication LED This LED will light up when the gas concentration level has reached the 300ppm concentration or when the accumulation level is reached The relay contact is closed and an impulsive sound is issued 4 Electrochemical Cell sensor for Carbon Monoxide detection 5 TEST button This button is used to simulat...

Страница 4: ... The relays are voltage free WARNING Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be incorporated in the elec...

Страница 5: ... 2 3 4 5 1 2 3 4 5 Solenoid valve NA Fan Fan Power Supply 230 VAC N Ph 1 2 3 4 5 Power Supply 230 VAC Fan Solenoid valve NA N C C NO NC C NO NC C NO One or more detectors with a normally close valve 230VAC Ph N 1 2 3 4 5 1 2 3 4 5 Solenoid valve NC Fan Fan Power Supply 230 VAC NC C NO NC C NO Electrical connections ...

Страница 6: ...to follow this scheme and keep in mind the following general regulations The CO922 is an equipment adapted to be mounted on a wall When installing is good to use reasonable care that requires an electronic device and then Install the detector away from sources of heat Avoid that the liquids may come into contact with the detector remembering that its box has a degree of protection IP42 The install...

Страница 7: ... does not exempt from the compliance with all regulations concerning the characteristics installation and use of gas appliances the ventilation of the spaces and the elimination of combustion products are described in the UNI norms according to ART 3 LAW 1083 71 and relevant legal provisions 1 Put out all free flames 2 Close the main gas tap or the LPG cylinder tap 3 Do not turn any lights on or o...

Страница 8: ...xcluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collect...

Отзывы: