Speed Masking
The masking of a defined speed window can be parameterized to avoid reso‐
nance frequencies of the machine or machine frame. The following parame‐
ters have to be configured.
Code
Name
Setting range
Default
Attri.
F4.57
Speed masking: Center speed
0...10,000 rpm
0
Run
F4.58
Speed masking: Window
0...10,000 rpm
0
Run
Tab. 7-7:
Parameter list of speed masking
F4.57 Speed masking: Center speed
The center speed defines the center of the speed window to be masked to
avoid resonance frequencies. The center speed should be the same value as
the major resonance frequency of the machine.
F4.58 Speed masking: Window
This parameter defines the width of the speed window to be masked to avoid
resonance frequencies.
The figure below visualizes the parameterization of the speed masking.
Fig. 7-28:
Parameterization of speed masking
The speed masking still takes the motor derating function from previous page
into account.
The speed masking is deactivated as soon as one of the two pa‐
rameters F4.57, F4.58 has the value "0".
Bosch Rexroth AG
DOK-SYTROX-DRN5020****-IT05-EN-P
80/143
Frequency-Controlled Pump Drive System Sytronix DRn 5020
Commissioning of Sytronix DRn 5020 System