7.5.5
Group F4: Motor and Pump Settings
Code
Name
Setting range
Default
Attri.
F4.00
Protection function control word
0...15
Bit0=0: Issues only a warning
Bit0=1: Motor stall detection sets motor
setpoint speed to zero on occurence
Bit3=0: Deactivate oil change detection
Bit3=1: Activate oil change detection
0
Run
F4.29
Pump type
0...31
1
Stop
F4.30
Pump: Maximum displacement
1.0...5,000.0 ccm
18.0
Stop
F4.47
Maximum torque limitation
200.0...400.0 %
200.0
Stop
F4.50
Pump: Maximum angular acceleration
0...60,000 rad/s
2
1,500
Stop
F4.51
Pump: Maximum speed
0...10,000 rpm
1,000
Stop
F4.52
Pump: Minimum speed
0...10,000 rpm
300
Stop
F4.53
Pump: Inertia mantissa
0...10,000 kgm
2
100
Stop
F4.54
Pump: Inertia exponent
0...10
5
Stop
F4.55
Motor derating: Continuous torque at standstill 0.00...100.00 %
0.00
Stop
F4.56
Motor derating: Limit speed
0...10,000 rpm
0
Stop
F4.57
Speed masking: Center speed
0...10,000 rpm
0
Run
F4.58
Speed masking: Window
0...10,000 rpm
0
Run
F4.59
Auxiliary pump: Displacement
0.0...5,000.0 ccm
0.0
Stop
F4.60
Auxiliary pump: Pressure
0.00...250.00 bar
0.00
Stop
F4.61
Motor stall detection: Pressure threshold
0...10,000 bar
20
Run
F4.62
Motor stall detection: Wait time
0...10,000 ms
3,000
Run
F4.63
Warning hours of oil change
0...60,000 hours
36,000
Run
F4.64
Error hours of oil change
0...60,000 hours
40,000
Run
F4.65
Oil in operation time hour
-
-
Read
F4.66
Reset oil in operation time
0...1
0
Run
F4.70
Threshold for oil level warning
(warning if analog input below limit)
0...10 V, 20 mA
0
Run
F4.71
Threshold for oil level error
(error if analog input below limit)
0...10 V, 20 mA
0
Run
F4.72
Threshold for oil temperature warning
(warning if analog input above limit)
0...10 V, 20 mA
0
Run
F4.73
Threshold for oil temperature error
(error if analog input above limit)
0...10 V, 20 mA
0
Run
F4.74
Oil cooler switching level
(switch on if analog input above limit)
0...10 V, 20 mA
0
Run