Load Motor Parameter
The parameters of MOT-FC_HOY motor are pre-configured in the ASF, so
that the auto tuning and motor parameterization is not required when the DRn
5020 application uses preconfigured "MOT-FC_HOY" motor. Please keep
[F1.15] = 1, and set F1.16 to the corresponding power level as specified be‐
low.
Code
Name
Setting range
Default
Attri.
F1.15
Motor type
0: Others
1: MOT-FC_HOY
0
Stop
F1.16
Motor power level
0: No selection
1: 0.2 kW
2: 0.3 kW
3: 0.5 kW
4: 0.7 kW
5: 1.1 kW
6: 1.5 kW
7: 2.2 kW
8: 3 kW
9: 4 kW
10: 5.5 kW
11: 7.5 kW
12: 11 kW
13: 15 kW
14: 18.5 kW
15: 22 kW
16: 30 kW
17: 37 kW
18: 45kW
19: 55 kW
20: 75 kW
21: 90 kW
0
Stop
Tab. 7-11:
Motor parameter list
●
Only change motor parameter by switching F1.16 to 1...21,
when F1.15 = 1.
●
If F1.15 = 0, no motor parameter will be changed by switch‐
ing F1.16.
If the motor parameters from F1.15 / F1.16 are selected, the following param‐
eters in EFC converter will be changed automatically.
Bosch Rexroth AG
DOK-SYTROX-DRN5020****-IT05-EN-P
86/143
Frequency-Controlled Pump Drive System Sytronix DRn 5020
Commissioning of Sytronix DRn 5020 System