7.5.7
Auto-modified EFC Parameters in ASF Initialization
Code
Name
Setting range
Default
Attri.
C0.00
Control mode
(EFC 5610 only)
0: V/f control
1: Sensorless vector control
1
Stop
E0.01
First run command source
0...2
1
Stop
E0.02
Second frequency setting source
0...99
0
Stop
E0.08
Maximum output frequency
50.00...400.00 Hz
100.00
Stop
E0.09
Output frequency high limit
[E0.10]...[E0.08] Hz
100.00
Run
E0.17
Direction control
0: Forward / Reverse
1: Forward only
2: Reverse only
3: Swap default direction
3
Stop
E0.26
Acceleration time
0.1...6,000.0 s
0.1
Run
E0.27
Deceleration time
0.1...6,000.0 s
0.1
Run
E1.00
X1 input
0...46
35
Stop
E1.01
X2 input
0...46
34
Stop
E1.40
AI2 input mode
0: 0...20 mA
1: 4...20 mA
2: 0...10 V
3: 0...5 V
4: 2…10 V
2
Run
E1.60
Motor temperature sensor channel
0: Inactive
1: AI1 analog input
2: AI2 analog input
3: EAI analog input
0
Stop
E2.15
Relay1 output selection
0...99
14
Stop
E2.25
AO1 output mode
0: 0...10 V
1: 0...20 mA
1
Run
E2.26
AO1 output setting
0: Output frequency
1: Setting frequency
2: Output current
4: Output voltage
5: Output power
6: AI1 analog input
7: AI2 analog input
8: EAI analog input
11: Motor temperature sensor power
supply
99: Inactive
0
Run
Tab. 7-32:
Auto-modified EFC parameter list
Bosch Rexroth AG
DOK-SYTROX-DRN5020****-IT05-EN-P
114/143
Frequency-Controlled Pump Drive System Sytronix DRn 5020
Commissioning of Sytronix DRn 5020 System