Threshold for Oil Level / Oil Temperature
Code
Name
Setting Range
Default
Attri.
F2.36
DO1 output
0: No function assigned from ASF
1: Converter warning
2: Green flashing LED
3: Red flashing LED
4: Cooler on
5: Heater on
1
Run
F2.37
EDO output
0
Run
F2.40
Relay 1 output
0
Run
F2.41
Extension relay output
0
Run
Tab. 7-16:
Parameter list of digital and relay output
The cooler and the heater are related to the oil temperature, please refer to
the parameters in the table above.
Code
Name
Setting Range
Default
Attri.
F4.70
Threshold for oil level warning
(warning if analog input below limit, see warning
d0.87, Bit 6)
0...10 V, 20 mA
0
Run
F4.71
Threshold for oil level error
(error if analog input below limit, see warning
d0.89, Bit 12)
0...10 V, 20 mA
0
Run
F4.72
Threshold for oil temperature warning
(warning if analog input above limit, see warning
d0.87, Bit 7)
0...10 V, 20 mA
0
Run
F4.73
Threshold for oil temperature error
(error if analog input above limit, see warning
d0.89, Bit 13)
0...10 V, 20 mA
0
Run
F4.74
Oil cooler switching level
(switch on if analog input above limit)
0...10 V, 20 mA
0
Run
F4.75
Oil heater switching level
(switch on if analog input below limit)
0...10 V, 20 mA
0
Run
Tab. 7-17:
Threshold for oil level / oil temperature
DOK-SYTROX-DRN5020****-IT05-EN-P
Bosch Rexroth AG
91/143
Frequency-Controlled Pump Drive System Sytronix DRn 5020
Commissioning of Sytronix DRn 5020 System