Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
67
23.
Used for the "outside switch" (i.e. the New Zealand FB silence
switch).
24.
The Addressable multipurpose I/O unit 3361 monitored Input 0
used as zone line input (Z).
11.2
Logic
The logic has to be set.
54
(•) Normally open / normally low
Normally open contact or
normally low optocoupler input.
( ) Normally closed / normally high
Normally closed contact or
normally high optocoupler input.
11.2.1
Supervised
Valid for the Inputs and Outputs expansion board (4583) program-
mable inputs (Input 0-4) only.
(•) Normally open (high resistance)
( ) Normally closed (low resistance)
Depending on the selected logic, Normally open (high resistance,
3K3)
or
Normally closed (low resistance, 680R), the function will be
according to the table on page 63.
54
In the WinG3 dialog box "Input".