Planning Instructions Fire alarm system EBL512 G3, V1.1.x
32
Fan
control
and indicating panel, for four Fan control panels, each
with six LEDs (On / Auto / Off / Running / Stopped / Fault) and
three push buttons (On / Auto / Off). One "Reset" switch.
Simple or Advanced function for a "Supply air fan" or a "Standard
fan". Enhanced function for a "Smoke exhaust", "Smoke spill",
"Stair pressurisation" or a "Supply air" fan.
This type is used with the "Fan control application board" 4594.
Zone
control
and indicating panel, with outputs and inputs for 16
zone LEDs (Alarm / Fault / Disabled) and 16 push buttons
(Disable).
For the number and type of boards that can be used, see page 26.
There is no COM loop address to be set. Instead, the
expansion
board no. / address
(0-7) is set with jumpers (
JP1-JP3
) on the I/O
Matrix board respectively. See Figure 5, page 27.
In EBL512 G3 can totally up to 200 outputs be used, including all
kinds of outputs.
For more information (e.g. application board type selected via jumpers
JP4-JP5), see the I/O Matrix board 4582, Technical description
MEW00914.
Each I/O Matrix board has to be added
via WinG3
....and
programmed
regarding:
Address
(shall be the same board no. as set via jumpers "JP1-
JP3"), see Figure 5, page 27.
Name
(I/O Matrix Board # - normally not changed)
LED test on Input 15
(selected or not selected)
The 4582 board has 48 LED outputs and 16 switch inputs (0-15).
Depending on the type (Generic, Fan or Zone), the outputs and inputs
are programmed differently.
Available application boards (fan control and general I/O boards), see
page 52.
6.5.1
Generic
Used for Application board type
Generic
, e.g. "General I/O
application board" 4596 (see page 52).
Each output (0-47) has to be added and programmed
via WinG3
regarding: