Planning Instructions Fire alarm system EBL512 G3, V1.1.x
125
18.4.1.4
Clean condition, level 1, 2 & 3
For this learning condition to be adapted there must be
no
check-mark
for
level 1
,
level 2
and
level 3
respectively during the
learning
period
, i.e. no check-mark what so ever.
The
Clean condition
will be ended directly if any
36h period
for
level 1
,
level 2
and
level 3
respectively gets a check-mark, i.e. any
check-mark what so ever.
18.4.1.5
Learning condition summary
A detector can adapt the following
learning conditions
, depending on
if and when
level 1
,
level 2
and
level 3
are exceeded or not:
Normal condition
(default)
or
Clean condition
or
Steam / tobacco condition
and/or
Heating condition
and/or
Cooking
condition
The following is valid for the different type of detectors:
4352
: This detector uses not the Learning function.
4350
: This detector uses the Learning function (for different alarm
threshold levels and alarm delay times, depending on smoke & temp.).
4301
: This detector uses not the Learning function.
4300
: This detector uses not the Learning function.
18.5
Alarm delay time
Depending on the detector type, mode and learning condition the
delay times before fire alarm threshold level was exceeded, are for the
different type of detectors:
4352
: Normally 9 seconds.
4350
:
#3
NOTE!
Max. alarm delay time is 60 seconds.