Planning Instructions Fire alarm system EBL512 G3, V1.1.x
73
13.2
Logic
(•) Normally open / low
Normally open relay contact or normally
low voltage output.
65
( ) Normally closed / high
Normally closed relay contact or
normally high voltage output (24V DC).
66
13.3
Supervised / Not supervised
A voltage output is supervised (default). By unmarking the
"Supervised" checkbox the voltage output will be not supervised.
A normally high output cannot be supervised.
13.4
Output signal period
Each output uses an "Output signal period", which controls the
output's activation. The following are available:
User defined 1-8 can be built up with type and time.
Types
:
0.
Steady (continuous)
1.
Intermittent
2.
Pulse
3.
Steady, Delayed Activation
4.
Intermittent, Delayed Activation
5.
Pulse, Delayed Activation
6.
Steady, Delayed De-Activation
Times
:
Delay time (when required)
Pulse length time (when required)
Pulse off time (when required)
De-activation time (when required)
65
The logic is set in the WinG3 dialog box "Voltage / Relayed Output".
66
The logic is set in the WinG3 dialog box "Voltage / Relayed Output".
NOTE!
A normally high output can not be supervised and it will be low for
a few seconds during restart of the c.i.e.