Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
124
Cooking condition, depending on the occurrence of smoke
together with rise of temperature, i.e.
level 3
=
2S+deltaT
>
10.
NOTE!
S has to be > 2.5 and deltaT has to be > 3.
Clean condition, the most sensitive condition requiring very
clean and stable environment, i.e. the values for all the other
conditions (level 1, 2 and 3) must not be exceeded.
18.4.1.1
Steam / tobacco condition, level 1
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
In a
learning period
there are twenty
36h-periods
(i.e. 20 x 36h =
720h = 30 days = one month).
During each
36h
-
period
it is recorded if
level 1
is exceeded at least
one time. If so, the
36h
-
period
will get a check-mark (see example).
If three or more of the
36h
-
periods
during the
learning period
have a
check-mark, the Steam / tobacco condition will be adapted. In the
example this happens in the
36h-period
no. 10 (i.e. after 10 x 36h =
360h).
After the
36h period
no. 20, the next
learning period
starts again in
the
36h period
no. 1. The check-marks are inherited from the
previous
learning period
. Depending on if
level 1
is exceeded during
the
36h period
respectively or not, there will be a check-mark or no
check-mark.
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
In the example, the Steam / tobacco condition will be ended after the
36h period
no. 3, since there are left only two
36h periods
with
check-marks in the
learning period
now. (If later, one or more
36h
periods
will get a check-mark, the Steam / tobacco condition will be
adapted again as long as three or more of the
36h
-
periods
during the
learning period have a check-mark.)
18.4.1.2
Heating condition, level 2
The learning function is the same as for the Steam / tobacco condition,
level 1
.
18.4.1.3
Cooking mode, level 3
The learning function is the same as for the Steam / tobacco condition,
level 1
.
Содержание EBL512 G3 5000