Planning Instructions Fire alarm system EBL512 G3, V1.1.x
66
12.
Activated input will generate a fault in EBL512 G3. Output with
trigger condition "Extinguishing system fault" will be activated.
The following fault message will be shown:
FAULT: Extinguishing system,
control unit xx
13.
Activated Extinguishing equipment feedback to the EBL512 G3
control unit to light up the LED "Extinguishing".
52
14.
Ext. fuses (for ext. power supply equipment) fault output will
activate a fault in the EBL512 G3 system. The following fault
message will be shown:
FAULT: External fuses, control unit xx
15.
Ext. power supply equipment fault output will activate a fault in
the EBL512 G3 system. The following fault message will be
shown:
FAULT: External power supply,
control unit xx
16.
Activated input (i.e. fault on the fault routing equipment) will
generate a fault in EBL512 G3:
FAULT: Fault warning routing equipment,
control unit xx
17.
A special detector, push button, etc. can activate a fire alarm in
EBL512 G3. Zone no. and Address (+ user definable alarm text).
18.
A feed-back from the equipment activated by the corresponding
interlocking output. Activated input is shown in menu H9/C1.
See also chapter "Interlocking function", page 84.
19.
"Loss of the battery charger to external power supply equipment"
fault output will activate a fault in the EBL512 G3 system. It will
have the same time delay, as set for the Loss of main power
source fault for the c.i.e. The following fault message will be
shown:
FAULT: Charging external power supply,
control unit xx
20.
"Loss of main power source to external power supply equipment"
fault output will activate a fault in the EBL512 G3 system. It will
have the same time delay, as set for the Loss of main power
source fault for the c.i.e. The following fault message will be
shown:
FAULT: Mains, external power supply,
control unit xx
21.
Default. Indicating that an input trigger condition is not selected,
i.e. the input will not "activate" anything.
22.
Pre-warning, e.g. from a High Sensitive Smoke Detector's pre-
warning output. Zone no. and Address have to be set to the same
as the corresponding fire alarm (from the same detector).