Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
150
Other units
Normal state
(quiescent) (mA)
Alarm state
(activated) (mA)
Routing equipment (Fire brigade tx / Fault tx)
Acc. to the producer
Acc. to the producer
External Presentation unit 1728
26
@24 V / 48@12 V
49
@24 V / 88@12 V
Alert Annunciation unit 1735 / 1736
26
@24 V / 48@12 V
42
@24 V / 79@12 V
External FBP 1826 / 1828
26
@24 V / 48@12 V
49
@24 V / 88@12 V
Printer 1835 (for ext. FBP 1826)
137
4
@24 V / 7@12 V
4
@24 V / 7@12 V
Alarm devices (sounders, etc.)
0
Acc. to the producer
Door release magnets
Acc. to the producer
0
Alert annunciation controller 1740
10
40
NOTE!
Regarding the 1728, 1735, 1736, 1826, 1828 and 1835 units,
see the next page.
137
When the printer is active the current consumption is 161 / 345 mA
momentarily.