Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
25
5.6
Relay outputs for routing equipment (tx)
Not programmable outputs. The outputs can be tested via menu H1,
see the EBL512 G3 Operating Instructions MEW01163. Connections
according to dwg 512 G3 – 24.
5.6.1
Fire alarm output
This output is normally used for fire alarm routing equipment (Fire
brigade tx). It is a change-over relay contact that will be activated
when a fire alarm is generated in the system
7
. Activated output is
(normally) indicated by the LED "Fire brigade tx".
8
5.6.2
Fault condition output
This output is normally used for fault warning routing equipment
(Fault tx). It is a change-over relay contact that is normally activated
and will be de-activated in case of a fault
9
in the control unit (c.i.e.)
10
.
De-activated output (i.e. fault condition) is indicated by the LED
Routing equipment
"Fault tx activated".
7
The output can be disabled via "door open" or via menu H2/B9. See also
chapter "Alert Annunciation", page 100.
8
This output and programmable outputs with type of output = Fire brigade
tx, will normally turn on the LED but a programmable input with trigger
condition = Activated routing equipment, can turn on the LED instead.
9
Also when the control unit is out of power (i.e. power supply and battery
out of work) or Watch-dog fault.
10
The output can be disabled via "door open" or via menu H2/B9.