Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
60
The unit shall be wall mounted. The LED "Acknowledge"
can be turned on by the push button "Acknowledge" or by an
input, i.e. a programmable output. This is set via a jumper
"JP1" in the unit. The unit is power supplied from EBL512
G3 or an external power supply. One supplementary
compression gland can be used for cable entry.
The unit has the following LEDs:
Fire
, indicating fire /
AA
alarm.
Operation
, indicating that the unit is in operation, i.e. the
AA
function is enabled in the system. A time channel can be used
to enable this function.
Fire brigade alerted
, indicating that the "Fire brigade tx"
output is activated in EBL512 G3 because:
-
the activated fire alarm is not an
AA
alarm
-
the
AA
function has been ended, e.g. the acknowledge or
investigation time has run out, etc.
Acknowledge
, indicating that the
AA
alarm has been
acknowledged.
The unit has the following push buttons:
Acknowledge
, used to acknowledge an
AA
alarm.
Reset
, used to reset an
AA
alarm.
Connections and more details are to be found in the Technical
Description MEW00283.
9.4.2
External LED
2218
Ext. LED (ext. indicator). Used when a detector is placed out
of view or hidden. The LED is lit at the same time as the LED
in the detector / base it is connected to. It has a "Burning
house" symbol instead of any text. 2218 can be connected to all
types of Panasonic detectors / bases. The input is polarised.
J2:1 (+5 to +35 V DC) for conventional detectors / bases
J2:2 (+; < 25 mA) for analog detectors / bases
J2:3 (0 V)
To be wall mounted (87 x 87 x 30 mm).
9.4.3
Alarm devices (sounders, etc.)
Regarding addressable alarm devices, see page 48.
In the Panasonic product range are no alarm devices intended for a
supervised (monitored) voltage output (e.g. S0 – S3 in EBL512 G3).
Connections of alarm devices according to drawing 512 G3 - 23.
(For addressable sounders, see page 48.
9.4.4
Door release magnets
In the Panasonic product range are no
Door release magnets. Door
release magnets shall always be provided with a "suppression diode"