Set the wanted number and the validation check in WinG3 can give a
"too many alarm points" warning. The validation check is
automatically performed when starting a download of SSD to the c.i.e.
Suppress buzzer during fault
: This check box shall be marked
if faults generated in other control units shall be suppressed in this
control unit, i.e. if the buzzer shall sound for faults generated in
this control unit only.
Use Pre-warning
: This check box shall be marked if the pre-
warning detection shall be enabled, i.e. pre-warnings will be
activated in this control unit and presented in all control units. All
programmable outputs in the system, with trigger condition "Pre-
warning", will be activated (if not disabled).
Checkbox not marked = Pre-warnings will not be activated in this
control unit.
19.2
WinG3 Control unit pop-up menu
Some commands might be disabled since you have to connect and log
on to the control unit to be able to select / use them.
19.2.1
Reset alarm counter
The control unit has an alarm counter that can be reset if required.
19.2.2
Software version
The control unit software (S/W) version will be displayed.
19.2.3
Upgrade number of alarm points
The control unit is by delivery be configured for 128, 256 or 512
alarm points. Any number of
alarm points
can be changed on site,
normally 128
256
512.