Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
71
12.6
The 3364 unit's VO0
– VO2
Each 3364 unit has two programmable, supervised (monitored)
55
voltage outputs:
Output
VO0
Supervised (monitored) voltage output, 24V DC
59
Output
VO1
Supervised (monitored) voltage output, 24V DC
59
Each 3364 unit also has one programmable special output, intended
for fire door closing (release magnets) only:
Output
VO2
Voltage output, 24 V DC, max. 1A
59
. Normally high.
For more information see the Technical Description MEW00529.
24 V DC
is required from an external power supply unit (e.g. 3366).
Connections and more information, see dwg. 512 G3 – 31 & - 38.
12.7
The 3377 unit's Output (siren)
Each 3377 unit has one programmable output:
Output
Siren
Three priority levels and three types of tones.
Connections and more information, see dwg. 512 G3 – 31.
12.8
The 3379 unit's Output (sounder)
Each 3378 unit has one programmable output:
Output
Sounder
Three priority levels and three types of tones.
Connections and more information, see dwg. 512 G3 – 31.
12.9
The 4380 unit's Output (beacon)
Each 4380 unit has one programmable output:
Output
Beacon
(Light output and flash rate are user selectable via
switches in the unit.)
Connections and more information, see dwg. 512 G3 – 31.
59
Cont. 1 A, during 10 ms 1.4 A.