Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
41
3339
Enclosed Addressable Manual Call Point.
23
3339 is like the
3333 unit but with another type of back-box (incl. a tightening
gasket). For surface mounting. For indoor use in premises
where IP56 rating is required. Operating temp. -10 to +55
°C.
9.1.1.3
Analog Detectors
3308
Analog heat detector. 3308 shall be plugged in an analog base
(3312 / 3312F / 3312FL / 4313). Built-in LED that is lit to
indicate that the detector has activated a fire alarm. Prepared
for mechanical lock (screw attached) – if required. The COM
loop address is set with the Address setting tool (3314). The
detector has an address label on which the programmed COM
loop address can be written.
The Address setting tool (3314) is also used for mode setting:
NORMAL mode
: 3308 is in this mode via WinG3 set to one
of three algorithms (static response temp. range) for class:
A1
(54-65°C),
min./
typical
/max. ambient temp. -20/
+25
/+50°C
A2 S
(54-70°C),
min./
typical
/max. ambient temp. -20/
+25
/+50°C
B S
(69-85°C),
min./
typical
/max. ambient temp. -20/
+40
/+65°C
2330 mode
: Not used in system EBL512 G3.
2312 mode
: Not used in system EBL512 G3.
3309
Analog heat detector. Enclosed (IP67)
24
. Built-in LED that is
lit to indicate that the detector has generated fire alarm.
Terminals for an ext. LED (2218). Recess for label holder
(3391). The COM loop address is set with the Address setting
tool (3314). The Address setting tool 3314 is also used for
mode setting:
NORMAL mode
: 3309 is in this mode via WinG3 set to one
of three algorithms (static response temp. range) for class:
A1
(54-65°C),
min./
typical
/max. ambient temp. -20/
+25
/+50°C
A2 S
(54-70°C),
min./
typical
/max. ambient temp. -20/
+25
/+50°C
B S
(69-85°C),
min./
typical
/max. ambient temp. -20/
+40
/+65°C
2330 mode
: Not used in system EBL512 G3.
2312 mode
: Not used in system EBL512 G3.
4300
Analog multi detector. 4300 is a smoke detector and a heat
detector within one housing. Scattered light (i.e. reflection of
infrared light) is used to detect
smoke
and the
heat
sensing
element is a thermistor. The detector unit (actually the heat
detector) can detect a methylated spirits (alcohol) fire (EN54-9,
test fire TF6; liquid fire), which normally is impossible for a
photo electric smoke detector to detect.
The detector has unleaded soldering.
Shall be plugged in an analog base (3312 / 3312F / 3312FL /
24
This detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 70°C), -20°C < T
a
< 65°C
.
Zone-Addr.
001-01 (smoke)
001-02 (heat)
COM loop address
e.g. 123
Содержание EBL512 G3 5000
Страница 2: ...This page has deliberately been left blank ...
Страница 167: ...This page has deliberately been left blank ...