Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
30
The I/O expansion board 4583 has two programmable supervised / not
supervised voltage outputs (Output 0-1), one special / programmable
output (Output 2) intended for German extinguishing system and five
programmable supervised / not supervised inputs (Input 0-4).
Connections to "J1:1-16" and "J2" according to drawing 512 G3 – 35,
sheet 1/2 and sheet 2/2.
Output 0-1 has to be programmed
via WinG3 regarding:
Type of output, i.e. output for Control, Alarm devices, etc.
Output signal period (steady, pulse, delay, etc.)
Supervised / Not supervised
16
Logic, i.e. normally low (default)
or
normally high (24 V DC)
17
.
Control expression (one or more trigger conditions)
One to five 33K resistors can be connected. When the connections are
finished, a calibration has to be done. Calibration value has to be in
the range 4K7-50K. See also the EBL512 G3 Operating Instructions
MEW01163 chapter "Calibration of supervised outputs (menu
H5/A1)".
Voltage
Output 0
(J1:1-2): Max. 200 mA (Fuse F1). Can be used for
German fire alarm routing equipment, fire alarm.
("E"
Brandmeldung)
Voltage
Output 1
(J1:5-6): Max. 200 mA (Fuse F2). Can be used for
German fire protection equipment / key cabinet.
("G"
FSK öffnen)
See also the WinG3 help or chapter "Programmable outputs", page 68.
Output 2 has to be programmed
via WinG3 regarding:
Type of output, i.e. output for Control, Alarm devices, etc.
Output signal period (steady, pulse, delay, etc.)
Logic, i.e. normally open (default)
or
normally closed.
Control expression (one or more trigger conditions)
Output 2
(J1:11-12): Normally open (high resistance, 3K3, when
supervised) or Normally closed (low resistance, 680R, when
supervised). Used for German extinguishing system
(Löschanlage)
.
See also the WinG3 help or chapter "Programmable outputs", page 68.
Input 0-4 have to be programmed
via WinG3 regarding:
Trigger condition (Triggered by)
Supervised / Not supervised
Logic, i.e. Normally open (high resistance, 3K3, when supervised)
or
Normally closed (low resistance, 680R, when supervised)
Additional information depending on the selected type
16
A normally high output can not be supervised. The supervision voltage is
1.5 – 3.6 V DC (depending on the number of supervision resistors) and the
polarity is reversed compared to an activated output.
17
Regarding the
system voltage
, see chapter "Power supply", page 150.