Planning Instructions Fire alarm system EBL512 G3, V1.1.x
104
16.13
Alarm Acknowledgement Facility (AAF)
This facility is used on the Australian market only.
The
AAF
function is similar to the "
A
lert
A
nnunciation function" (see
page 102).
One AAF zone can consist of one to five analog smoke detectors
(4300 / 4301), one AAF buzzer (e.g. Sounder base 3379) and one
AAF Control (AAFC)
98
. All connected on one COM loop.
Sounder Base 3379
Smoke detector (4300, 4301)
COM loop
AAF
Non-latching switch
LED
PRESS TO ACKNOWLEDGE
FALSE ALARM
AAFC
Figure 22. Alarm Acknowledgement Facility units.
AAF function (see also the flow chart in the following figure):
- One of the detectors in an AAF zone reaches its fire alarm level.
The
AA
Process starts and the AAF buzzer sounds.
- The
A
cknowledgement
P
eriod starts
(
A
Period=10-60 sec. -- programmable via WinG3).
- If it is a false alarm, acknowledge the alarm on the AAFC before
the
A
Period is ended.
- After acknowledgement an
I
nvestigation
P
eriod starts and the AAF
buzzer is silent
(
I
Period =0-3 min. -- programmable via WinG3).
The AA Process ends if all the detectors in the AAF zone becomes
normal again (goes below its fire alarm level) during the
I
Period.
If the
A
or
I
Periods run out during the
AA
Process and any detector
in the AAF zone still is over its fire alarm level, normal fire alarm(s)
will be activated.
98
This unit is available on the Australian market only.