Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
113
NOTE!
If any alarm point shall have a different alarm text in one or
more of the "display units" 1826, 1828, 1735, 1736 or 1728
110
, the text
has to be typed in the WinG3 "Text editor",
for the "display unit"
respectively
(Properties | Edit texts…):
Explanations (Text editor for
one
specific "display unit"):
Zone-Address
column
Shows the already programmed alarm points (e.g. 001-01, 001-02,
002-01 etc.).
Shows the already programmed zones, i.e. I/O unit 3361 zone line
inputs programmed with address "00" (i.e. as ZZZ –
00)
and 8 zones
expansion board 4580 zone line inputs.
Text in control unit
column
Shows already programmed alarm texts for each alarm point / zone.
This is information only and cannot be edited. These texts will be
displayed in the c.i.e. and all "display units" 1826, 1828, 1735, 1736
and 1728 if there are no other texts programmed in the "Text column".
Text
column
The text to be shown in
this
"display unit" for the alarm point / zone
respectively, has to be typed (edited) here.
NOTE!
In this "display
unit" this text will now be shown instead of the text in the "Text in
control unit" column, for the alarm point / zone respectively.
16.27.2
Downloading alarm texts to the DU:s 1728 / 1735 /
1736 and ext. FBP:s 1826 / 1828
The texts will be downloaded when the site specific data (SSD) is
downloaded via WinG3.
The unit respectively has to be set in S/W mode xxxx –
1587
16.28
Real time clock (RTC)
Each control unit has an RTC. It is used for (date) and time
presentation for fire alarms, faults, event logging and the time
channels 2-14. In a system with two or more control units in a TLON
network is the time in all control units synchronised.
111
110
Regarding text priority order etc. see Technical Description (chapt. "User
definable text messages") for the "display unit" respectively.
111
The calendar and clock can be set in any c.i.e. for the whole system.
Every day (at midnight) all calendars and clocks will be synchronised.