Parallel I/O connection
ZW User's Manual
163
6
Commun
ication
s with Exte
rnal De
vi
ces
Zero reset
Explanation of operations
(1) The ZERO input is turned ON.
(2) After the ZERO input time, the ZERO input is turned OFF.
(3) After the ZERO input is turned OFF, the zero reset is executed and the judgment results reflected in the
measurement results are output.
(4) The ZERO input is turned ON.
(5) After at least the cancel time of ZERO input has passed, the zero reset is cancelled.
Item
Min.
Max.
T7
Input response time
2 ms+T0
3 ms+T0×2
T13
ZERO input time
50 ms
0.8s
T14
ZERO input cancel time
1 s
(1)
(2)
(4)
(3)
T14
T13
T7
(5)
ON
OFF
Judgment output
(HIGH/PASS/LOW)
ZERO input