Stopping Methods
Selecting the Stopping Method when a Stop Command is Input
There are four methods of stopping the Inverter when a stop command is input:
•
Deceleration to stop
•
Coast to stop
•
DC braking stop
•
Coast to stop with timer
Set parameter b1-03 to select the Inverter stopping method.
Related Parameters
Param-
eter-
number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
LCD Display
b1-03
Stopping method selec-
tion
Select stopping method when stop com-
mand is sent.
0: Deceleration to stop
1: Coast to stop
2: DC braking stop (Stops faster than coast
to stop, without regenerative operation.)
3: Coast to stop with timer (Run commands
are ignored during deceleration time.)
0 to 3
0
No
Q
Stopping Method
b2-01
Zero speed level (DC
injection braking start-
ing frequency)
Set the frequency to start the DC injection
braking in units of Hz when deceleration to
stop is selected.
DC injection braking starts from E1-09
when b2-01 < E1-09.
0.0 to
10.0
0.5 Hz
No
A
DCInj Start Freq
b2-02
DC injection braking cur-
rent
Set the DC injection braking current as a
percentage, taking the Inverter rated current
as 100%.
0 to
100
50%
No
A
DCInj Current
b2-04
DC injection braking
time at stop
Set the DC injection braking time at stop.
Use when stopping if rotations continue due
to momentum.
Set to 0.00 to disable DC injection braking
time at stop.
0.00
to
10.00
0.50 s
No
A
DCInj Time @Stop