Parameter Tables
5
-
37
U: Monitor Parameters
The following settings are made with the monitor parameters (U parameters): Setting parameters for monitor-
ing in drive mode.
Status Monitor Parameters: U1
T1-04
Motor rated
current
Set the rated current of the motor
in Amps.
0.32 to
6.40
1.90 A
No
A
704H
4-8
Rated Current
Param-
eter-
Number
Name
Description
Output Signal Level During Multi-
Function Analog Output
Min.
Unit
Access
Level
RS-422A/
485
Register
LCD
Display
U1-01
Frequency
reference
Monitors/sets the frequency ref-
erence value.*
10 V: Max. frequency
(0 to + 10 V possible)
0.00
Hz
A
40H
Frequency
Ref
U1-02
Output fre-
quency
Monitors the output frequency.*
10 V: Max. frequency
(0 to + 10 V possible)
0.00
Hz
A
41H
Output Freq
U1-03
Output current
Monitors the output current.
10 V: Inverter rated output
current
(0 to +10 V, absolute value
output)
0.0
A
A
42H
Output Cur-
rent
U1-06
Output volt-
age
Monitors the output voltage refer-
ence value in the Inverter.
10 V: 200 VAC (400 VAC)
(0 to +10 V output)
0.0
V
A
45H
Output Volt-
age
U1-07
DC bus volt-
age
Monitors the main DC voltage in
the Inverter.
10 V: 400 VDC (800 VDC)
0 V
A
46H
DC Bus Volt-
age
U1-08
Output power
Monitors the output power (inter-
nal detected value)
10V: Inverter maximum
capacity (max. appli-
cable motor capacity)
(0 to +10 V possible)
0.0
kW
Output kWatts
U1-10
Input terminal
status
Shows input ON/OFF status.
(Cannot be output.)
-
A
49H
Input Term Sts
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD
Display
1: FWD command
(S1) is ON
1: REV command
(S2) is ON
1: Multi input 1
(S3) is ON
1: Multi input 2
(S4) is ON
1: Multi input 3
(S5) is ON
1: Multi input 4
(S6) is ON
1: Multi input 5
(S7) is ON