6
-50
Monitor Parameters
Using the Analog Monitor Parameters
This section explains the analog monitor parameters.
Related Parameters
Selecting Analog Monitor Items
The digital operator monitor items (U1-
oo
[status monitor]) are output from multi-function analog output ter-
minals FM-AC and AM-AC. Refer to Chapter 5 Parameters and set the values for the
part of U1-
(status monitor).
Param-
eter-
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
LCD Display
H4-01
Monitor selection (terminal
FM)
Sets the number of the monitor item to be output (U1-
)
at terminal FM.
4,10 to 14, 28, 34, 39, 40 cannot be set.
1 to 38
2
No
A
Terminal FM Sel
H4-02
Gain (terminal FM)
Sets the multi-function analog output 1 (FM) voltage level
gain.
Sets whether the monitor item output will be output in
multiples of 10 V.
The maximum output from the terminal is 10 V. A meter
calibration function is available.
0 ~ 100%
100%
Yes
Q
Terminal FM Gain
H4-03
Bias (terminal FM)
Sets the multi-function analog output 1 voltage level bias.
Sets output characteristic up/down parallel movement as a
percentage of 10 V.
The maximum output from the terminal is 10 V. A meter
calibration function is available.
-110.0 ~
+110.0%
0.0%
Yes
A
Terminal FM Bias
H4-04
Monitor selection (terminal
AM)
Sets the number of the monitor item to be output (U1-
) from terminal AM.
4,10 to 14, 28, 34, 39, 40 cannot be set.
1 to 38
3
No
A
Terminal AM Sel
H4-05
Gain (terminal AM)
Set the voltage level gain for multi-function analog output
2.
Set the number of multiples of 10 V to be output as the
100% output for the monitor items. The maimum output
from the terminal is 10 V. A meter calibration function is
available.
0 ~ 100%
50%
Yes
Q
Terminal AM Gain
H4-06
Bias (terminal AM)
Set the multi-function analog output 2 voltage level bias.
Sets output characteristic up/down parallel movement as a
percentage of 10 V.
The maximum output from the terminal is 10 V. A meter
calibration function is available.
-110.0 ~
+110.0%
0.0%
Yes
A
Terminal AM Bias
H4-07
Analog output 1 signal level
selection (FM)
Sets the signal output level for multi-function output 1
(terminal FM)
0: 0 to 10 V output
2: 4 to 20 mA
0 or 2
0
No
A
AO Level Select 1
H4-08
Analog output signal 2 level
selection (AM)
Sets the signal output level for multi-function output 2
(terminal FM)
0: 0 to 10 V output
2: 4 to 20 mA
0 or 2
0
No
A
AO Level Select 2