Adjusting Frequency References
6
-
25
The relationship between the output frequency and the jump frequency reference is as follows:
Fig 6.25 Jump Frequency
Setting Precautions
•
Set the jump frequency according to the following formula: d3-01
≥
d3-02
≥
d3-03 > Analog input.
•
When parameters d3-01 to d3-03 are set to 0 Hz, the jump frequency function is disabled.
Output
frequency
Frequency reference descending
Jump Bandwidth d3-04
Jump frequency reference
Frequency
reference
ascending
Jump
Bandwidth
d3-04
Jump
Bandwidth
d3-04
Jump freq
3 (d3-03)
Jump freq
2 (d3-02)
Jump freq
1 (d3-01)