4
-6
Basic Settings
Switch to the quick programming mode (the QUICK indicator on the Digital Operation should be lit) and then
set the following parameters.
Refer to Chapter 3 Digital Operator and Modes for Digital Operator operating procedures and to Chapter 5
Parameters and Chapter 6 Parameter Settings by Function for details on the parameters.
Table 4.1 Parameters that must be set
Class l : Must be set.
O
: Set as required.
Class
Parame-
ter Num-
ber
Name
Description
Setting
Range
Factory
Setting
Page
l
b1-01
Reference selec-
tion
Set the frequency reference input
method.
0: Digital Operator
1: Control circuit terminal (analog
input)
2: RS-422A/485 communications
3: Option Card
0 to 3
1
5-8
6-4
6-46
6-54
l
b1-02
Operation
method selection
Set the run command input method.
0: Digital Operator
1: Control circuit terminal (sequence
input)
2: RS-422A/485 communications
3: Option Card
0 to 3
1
5-8
6-8
6-46
6-54
O
b1-03
Stopping method
selection
Select stopping method when stop com-
mand is sent.
0: Deceleration to stop
1: Coast to stop
2: DC braking stop
3: Coast to stop with timer
0 to 3
0
5-8
6-10
l
C1-01
Acceleration time
1
Set the acceleration time in seconds for
the output frequency to climb from 0% to
100%.
0.0 to 6000.0
10.0 s
5-13
6-17
l
C1-02
Deceleration time
1
Set the deceleration time in seconds for
the output frequency to fall from 100% to
0%.
0.0 to 6000.0
10.0 s
5-13
6-17
O
C6-02
Carrier fre-
quency selection
The carrier frequency is set low if the
motor cable is 50 m or longer or to
reduce radio noise or leakage current.
0 to D, F
F
5-15
O
d1-01 to
d1-04 and
d1-17
Frequency refer-
ences 1 to 4 and
jog frequency ref-
erence
Set the required speed references for
multi-step speed operation or jogging.
0 to 120.00 Hz
d1-01 to
d1-04:
0.00 Hz
d1-17:
6.00 Hz
5-16
6-6
l
E1-01
Input voltage set-
ting
Set the Inverter's nominal input voltage
in volts.
155 to 255 V
(200 V class)
310 to 510 V
(400 V class)
200 V
(200 V
class)
400 V
(400 V
class)
5-18
6-74