Run Command
This section explains input methods for the run command.
Selecting the Run Command Source
Set parameter b1-02 to select the source for the run command.
Related Parameters
Performing Operations Using a Digital Operator
When b1-02 is set to 0, you can perform Inverter operations using the Digital Operator keys (RUN, STOP,
JOG and FWD/REV). For details on the Digital Operator, refer to Chapter 3 Digital Operator and Modes.
Performing Operations Using Control Circuit Terminals
When b1-02 is set to 1, you can perform Inverter operations using the control circuit terminals.
Performing Operations Using a 2-wire Sequence
The factory setting is set to a 2-wire sequence. When control circuit terminal S1 is set to ON, forward opera-
tion will be performed and when S1 is turned OFF, the Inverter will stop. In the same way, when control cir-
cuit terminal S2 is set to ON, reverse operation will be performed and when S2 is turned OFF, the Inverter will
stop.
Fig 6.9 2-wire Sequence Wiring Example
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
LCD Display
b1-02
Operation method selec-
tion
Set the run command source.
0: Digital operator
1: Control circuit terminal (sequence
input)
2: RS-422A/485 communications
3: Option Card
0 to 3
1
No
Q
Run Source
Inverter
Forward/Stop
Reverse/Stop
Sequence common