5
-34
o1-03
Frequency
units of refer-
ence setting
and monitor
Sets the units that will be set and
displayed for the frequency refer-
ence and frequency monitor.
0:
0.01 Hz units
1:
0.01% units (Maximum out-
put frequency is 100%)
2 to 39:
r/min units (Sets the motor
poles.)
40 to 39999:
User desired display
Set the desired values for setting
and display for the max. output
frequency.
Example: When the max. output
frequency value is 200.0, set
12000
0 to
39999
0
No
A
502H
6-80
Display Scal-
ing
o1-05
LCD-Bright-
ness
1: light
2:
3: normal
4:
5: dark
0 to 5
3
Yes
A
509H
LCD Contrast
Parame-
ter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD
Display
Set digit number
excluding the decimal
point.
Set the number of
digits below the
decimal point to
display.