Parameter Tables
5
-
19
Motor Setup: E2
* 1. The factory setting depends upon the Inverter capacity. The value for a 200 V class Inverter of 0.4 kW is given.
* 2. The setting range is 10% to 200% of the Inverter's rated output current. The value for a 200 V class Inverter of 0.4 kW is given.
Option Parameters: F
Communications Option Cards: F6
Param-
eter-
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD
Display
E2-01
Motor rated
current
Sets the motor rated current.
These set values will become the
reference values for motor pro-
tection, torque limits and torque
control.
This parameter is an input data
for autotuning.
0.32 to
6.40
*2
1.90 A
*1
No
Q
30EH
6-33
6-73
Motor Rated
FLA
E2-05
Motor line-to-
line resistance
Sets the motor phase-to-phase
resistance in
Ω
units.
This parameter is automatically
set during autotuning.
0.000
to
65.000
9.842
Ω
*1
No
A
312H
6-73
Term
Resistance
Param-
eter-
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD
Display
F6-01
DeviceNet
fault opera-
tion selection
Set the stopping method for com-
munications errors.
0: Deceleration to stop using
deceleration time in C1-02
1: Coast to stop/fault detection
2: Decelerates to stop using C1-
09 deceleration time/fault
detection
3: Continuous operating/alarm
detection
0 to 3
1
No
A
3A2H
-
Comm Bus Flt
Sel
F6-02
Communica-
tions external
fault input
detection
method selec-
tion
0: Fault detection during power
ON
1: Fault detected during running
only
0 or 1
0
No
A
3A3H
-
EF0 Detection
F6-03
Communica-
tions external
fault input
operation
selection
0: Deceleration to a stop using
C1-02 deceleration time/fault
detection
1: Coast to stop/fault detection
2: Decelerates to a stop using
C1-09 deceleration time/fault
detection
3: Continuous operating/alarm
detection
0 to 3
1
No
A
3A4H
-
EF0 Fault
Action
F6-05
Display
unit selection
for
Current moni-
tor
Sets the unit of current monitor
0: Ampere
1: 100%/8192
0 or 1
0
No
A
3A6H
-
Current Unit
Sel