6
-44
Related Parameters
Application Precautions
•
The number of auto restarts counter is reset under the following conditions:
After auto restart, normal operation has continued for 10 minutes.
After the protection operation has been performed and the error has been verified and an error reset
has been input.
After the power supply is turned OFF and then ON again.
Param-
eter-
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
LCD Display
L5-01
Number of auto restart
attempts
Set the number of auto restarts attempts.
Automatically restarts after a fault and conducts a speed
search from the run frequency.
0 to 10
0
No
A
Num of Restarts
L5-02
Auto restart operation
selection
Sets whether a fault contact output is activated during
fault restart.
0: No output (Fault contact is not activated.)
1: Output (Fault contact is activated.)
0 or 1
0
No
A
Restart Sel