Factory Settings that Change with the Inverter Capacity (o2-04)
200 V Class Inverters
Param-
eter-
Number
Name
Unit
Factory Setting
-
Inverter Capacity
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
o2-04
kVA selection
-
0
1
2
3
4
5
6
7
8
b8-04
Energy-saving coeffi-
cient
-
288.20
223.70
169.40
156.80
122.90
94.75
72.69
70.44
63.13
C4-02
Torque compensation
primary delay time
ms
200
200
200
200
200
200
200
200
200
C6-02
Carrier frequency selec-
tion
-
6
6
6
6
6
6
6
6
6
E2-01
Motor rated current
A
1.90
3.30
6.20
8.50
14.00
19.60
26.60
39.7
53.0
E2-05
Motor line-to-line resis-
tance
Ω
9.842
5.156
1.997
1.601
0.771
0.399
0.288
0.230
0.138
L2-02
Momentary power loss
ridethru time
s
0.1
0.1
0.2
0.3
0.5
1.0
1.0
1.0
2.0
L2-03
Min. baseblock (BB)
time
s
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
L2-04
Voltage recovery time
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L8-02
Overheat pre-alarm level
°
C
95
95
95
95
95
95
95
95
95