5
-8
Application Parameters: b
The following settings are made with the application parameters (B parameters): Operation Method Selection,
DC injection braking, speed searching, timer functions, dwell functions and energy saving functions.
Operation Mode Selections: b1
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD
Display
b1-01
Reference
selection
Set the frequency reference
input method.
0: Digital Operator
1: Control circuit terminal
(analog input)
2: RS-422A/485 communi-
cations
3: Option Card
0 to 3
1
No
Q
180H
4-6
6-4
6-46
6-54
Reference-
Source
b1-02
Operation
method selec-
tion
Set the run command input
method.
0: Digital Operator
1: Control circuit terminal
(sequence input)
2:RS-422A/485 communi-
cations
3: Option Card
0 to 3
1
No
Q
181H
4-6
6-8
6-46
6-54
Run Source
b1-03
Stopping
method selec-
tion
Used to set the stopping
method used when a stop
command is input.
0: Ramp to stop
1: Coast to stop
2: DC injection braking stop
(Stops faster than coast to
stop, no regenerative ope-
ration.)
3: Coast to stop with timer
(Run commands are dis-
regarded during decelera-
tion.)
0 to 3
0
No
Q
182H
4-6
6-10
Stopping
Method
b1-07
Operation
selection after
switching to
remote mode
Used to set the operation
mode by switching to the
Remote mode using the
Local/Remote Key.
0: Run signals that are input
during mode switching
are disregarded. (Input
Run signals after swit-
ching the mode.)
1: Run signals become
effective immediately
after switching to the
Remote mode.
0 or 1
0
No
A
186H
-
LOC/REM
RUN Sel
b1-08
Run com-
mand selec-
tion in
programming
modes
Used to set an operation
interlock in programming
modes.
0: Cannot operate.
1: Can operate (Disabled
when Digital Operator is
set to select run command
(when b1-02 = 0)).
0 or 1
0
No
A
187H
-
RUN CMD at
PRG