6
-58
Data Tables
The data tables are shown below. The types of data are as follows: Reference data, monitor data and broadcast
data.
Reference Data
The reference data table is shown below. You can both read and write reference data.
Register No.
Contents
0000H
Reserved
0001H
Frequency reference
Bit 0
Run/stop command
1: Run 0: Stop
Bit 1
Forward/reverse operation
1: Reverse 0: Forward
Bit 2
External error
1: Error (EFO)
Bit 3
Error reset
1: Reset command
Bit 4
ComNet
Bit 5
ComCtrl
Bit 6
Multi-function input command 3
Bit 7
Multi-function input command 4
Bit 8
Multi-function input command 5
Bit 9
Multi-function input command 6
Bit A
Multi-function input command 7
Bits B to F
Not used
0002H
Frequency reference (Set units using parameter o1-03)
0003H to 0005H
Not used
0006H
Not used
0007H
Analog output 1 setting (0 V/0 to 11 V/726)
→
10V = 660
0008H
Analog output 2 setting (0 V/0 to 11 V/726)
→
10V = 660
0009H
Multi-function contact output setting
Bit 0
Contact output 1 (Terminal M1-M2)
1: ON 0: OFF
Bit 1
Contact output 2 (Terminal M3-M4)
1: ON 0: OFF
Bit 2
Not used
Bits 3 to 5
Not used
Bit 6
Set error contact (terminal MA-MC) output using bit 7. 1: ON 0: OFF
Bit 7
Error contact (terminal MA-MC)
1: ON 0: OFF
Bits 8 to F
Not used
000AH to 000EH Not used