5
-18
Motor Costant Parameters: E
V/f Pattern: E1
* 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 2. E1-11 and E1-12 are disregarded when set to 0.0.
* 3. E1-13 is set to the same value as E1-05 by autotuning.
Param-
eter-
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD Diplay
E1-01
Input volt-
age setting
Sets the Inverter input voltage.
This setting is used as a reference
value in protection functions.
155 to
255
*1
200 V
*1
No
Q
300H
4-6
6-74
Input Volt-
age
E1-03
V/F pattern
selection
0 to D: Select from the 14 preset
patterns.
F:
Custom user-set patterns
(Applicable for settings
E1-04 to E1-10.)
0 to D,
F
F
No
Q
302H
6-74
V/F
Selection
E1-04
Max. output
frequency
To set V/f characteristics in a
straight line, set the same values
for E1-07 and E1-09. In this case,
the setting for E1-08 will be disre-
garded.
Always ensure that the four fre-
quencies are set in the following
manner:
E1-04 (FMAX)
≥
E1-06 (FA) >
E1-07 (FB)
≥
E1-09 (FMIN)
0.0 to
120.0
50.0
Hz
No
Q
303H
6-74
Max
Frequency
E1-05
Max. volt-
age
0.0 to
255.0
*1
200.0
V
*1
No
Q
304H
6-74
Max. volt-
age
E1-06
Base fre-
quency
0.0 to
120.0
50.0
Hz
No
Q
305H
6-74
Base fre-
quency
E1-07
Mid. output
frequency
0.0 to
120.0
2.5 Hz
No
A
306H
6-74
Mid. Fre-
quency A
E1-08
Mid. output
frequency
voltage
0.0 to
255
*1
15.0 V
*1
No
A
307H
6-74
Mid. Volt-
age A
E1-09
Min. output
frequency
0.0 to
120.0
1.2 Hz
No
Q
308H
6-74
Min Fre-
quency
E1-10
Min. output
frequency
voltage
0.0 to
255.0
*1
9.0 V
*1
No
A
309H
4-13
6-74
Min
Voltage
E1-11
Mid. output
frequency 2
Set only to fine-adjust V/f for the
output range. Normally, this setting
is not required.
0.0 to
120.0
0.0 Hz
*2
No
A
30AH
6-74
Mid Fre-
quency B
E1-12
Mid. output
frequency
voltage 2
0.0 to
255.0
*1
0.0 V
*2
No
A
30BH
6-74
Mid Voltage
B
E1-13
Base volt-
age
0.0 to
255.0
*1
0.0 V
*3
No
A
30CH
6-74
Base volt-
age
Output voltage (V)