-86
Prohibiting Writing Parameters from the Digital Operator
If you set A1-01 to 0, you can refer to and set the A1 and A2 parameter groups and refer to drive mode, using
the Digital Operator.
If you set one of the parameters H1-01 to H1-05 (multi-function contact input terminal S3 to S7 function
selection) to 1B (write parameters permitted), you can write parameters from the digital operator when the ter-
minal that has been set is ON. When the set terminal is OFF, writing parameters other than the frequency ref-
erence is prohibited. You can, however, reference parameters.
Setting a Password
When a pasword is set in A1-05, if the set values in A1-04 and A1-05 do not match, you can not refer or
change the settings of parameters A1-01 to A1-03.
You can prohibit the setting and referencing of all parameters except A1-00 by using the password function in
combination with setting A1-01 to 0 (Monitor only).
Related Parameters
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
LCD DIsplay
A1-01
Parameter access level
Used to set the parameter access level (set/read.)
0: Monitoring only (Monitoring drive mode and setting
A1-01 and A1-04.)
2: ADVANCED
(Parameters can be read and set in both quick pro-
gramming mode and advanced programming (A)
mode.)
0 or 2
2
Yes
A
Acces Level
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
LCD Display
A1-01
Parameter access level
Used to set the parameter access level (set/read.)
0: Monitoring only (Monitoring drive mode and setting
A1-01 and A1-04.)
2: ADVANCED
(Parameters can be read and set in both quick pro-
gramming mode and advanced programming (A)
mode.)
0 or 2
2
Yes
A
Acces Level
A1-04
Password
Password input when a password has been set in A1-05.
This function write-protects some parameters of the initial-
ize mode.
If the password is changed, A1-01 to A1-03 parameters
can no longer be changed. (Programming mode parame-
ters can be changed.)
0 to
9999
0
No
A
Enter Password
A1-05
Password setting
Used to set a four digit number as the password.
This parameter is not usually displayed. When the pass-
word (A1-04) is displayed, hold down the reset key and
press the Menu key and the password will be displayed.
0 to 9999
0
No
A
Select password