5
-16
Reference Parameters: d
Preset Reference: d1
Note The unit is set in o1-03 (frequency units of reference setting and monitor, default: 0.01 Hz).
Reference Limits: d2
Param-
eter-
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD
Display
d1-01
Frequency
reference 1
Sets the frequency reference in
the units used in o1-03.
0 to
50.00
0.00
Hz
Yes
Q
280H
4-7
6-6
Reference 1
d1-02
Frequency
reference 2
The frequency reference when
multi-step speed command 1 is
ON for a multi-function input.
0.00
Hz
Yes
Q
281H
4-7
6-6
Reference 2
d1-03
Frequency
reference 3
The frequency reference when
multi-step speed command 2 is
ON for a multi-function input.
0.00
Hz
Yes
Q
282H
4-7
6-6
Reference 3
d1-04
Frequency
reference 4
The frequency reference when
multi-step speed commands 1 and
2 are ON for multi-function
inputs.
0.00
Hz
Yes
Q
283H
4-7
6-6
Reference 4
d1-17
Jog fre-
quency refer-
ence
The frequency reference when
the jog frequency reference selec-
tion, FJOG command or RJOG
command is ON.
6.00
Hz
Yes
Q
292H
4-6
6-48
Jog
Reference
Param-
eter-
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD
Display
d2-01
Frequency
reference
upper limit
Set the output frequency upper
limit as a percentage of the max.
output frequency.
0.0 to
110.0
100.0%
No
A
289H
6-26
Ref Upper
Limit
d2-02
Frequency
reference
lower limit
Sets the output frequency lower
limit as a percentage of the maxi-
mum output frequency.
0.0 to
110.0
0.0%
No
A
28AH
6-26
Ref Lower
Limit
d2-03
Master speed
reference
lower limit
Set the master speed reference
lower limit as a percentage of the
max. output frequency.
0.0 to
110.0
0.0%
No
A
293H
6-26
Ref1 Lower